  • ONICON System-40 BTU Measurement

    Description

    The System-40 provides highly accurate thermal energy measurement in chilled water, hot water or condenser water systems. It is provided as a complete meter and includes a matched pair of platinum RTD temperature sensors and an integral inline ultrasonic flow sensor. It is available for use in ½” through 2½” piping systems with flow rates ranging from 0.03 to 250 GPM.

    Application

    Monitoring chilled water, hot water and condenser water in AHU and CRAC units for:

    •  Commercial office tenant billing
    •  Residential apartment and condominium tenant billing

    Monitoring renewable energy resources for:

    • Solar thermal applications
    • Ground source heat pumps
    • Geothermal heating systems

    Features

    • Reliable No-Moving-Parts Design – 
      • Wetted transducers measure the ultrasonic signal transit time differential, which correlates directly to the flow rate. The direct beam path orientation significantly enhances signal strength and long term reliability.
    • Highly Accurate Over a Wide Flow Range –
      • The flow sensor is accurate to within ±1% of reading over the normal (25:1 turndown)
      • operating range and within ±2% of reading over an extended (100:1 turndown) range.
    • User-Friendly Backlit Display – 
      • The bright, easy-to-read, backlit display uses “smart button technology” to simplify page navigation and programming. This eliminates the need for special configuration tools.
    • Matched Platinum 1000Ω RTD Temperature Sensors
      • Sensors are paired in a matching process that ensures a differential measurement uncertainty of better than ±0.18°F.
    • Suitable for Water and Water/Glycol Solutions
      • System-40 is field programmable for both water and water/glycol solutions to ensure accurate flow and energy measurement.
    • Detachable Display
      • The display for the system-40 is easily detached from the flow sensor. This allows for remote mount installation up to 5ft from the sensor body. 
    • Built-in Interval Data Logger
      • Energy and volume totals are date/time stamped and logged within the meter along with other analytical data. This data is available via BACnet®.
    • ACCURACY
      • ±1% of reading over 25:1 turndown
      • ±2% of reading over 100: 1 turndown
      • Overall turndown exceeds 500: 1
      • Repeatability: ≤±0.2%
      • Meets EN1434 Class 1 accuracy requirements
    • TEMPERATURE SENSORS 
      • Field serviceable MID certified matched pair of 2-wire 1000Ω platinum RTDs
      • Calibrated to a differential measurement uncertainty of ±0.18°F
      • Meets EN1434/C900.1 accuracy requirements for 3K sensors
    • CALCULATOR 
      • Computation error: ≤ 0.09% at 30°F Δt
      • Meets EN1434 Class 1 requirements with 3K minimum Δt
    • PIPE SIZE RANGE 
      • ½ – 2½” nominal diameter
    • PIPING SYSTEM CONNECTIONS 
      • Male NPT threads 
      • 2½” meter provided with ANSI Class 150 raised face flanges
    • FLUID TEMPERATURE RANGE 
      • 32 to 250°F
    • MAXIMUM OPERATING PRESSURE 
      • 400 psi
    • PRESSURE DROP 
      • Less than 1 psi at 4 ft/s, decreasing at lower velocities
    • MATERIALS 
      • Wetted components: Lead-free brass, PEEK
      • Enclosure: Polycarbonate
    • ENVIRONMENTAL 
      • Meets EN1434/C900.1 Class A requirements
      • Operating Temperature Range: -13 to 131°F
      • Storage Temperature Range: -14 to 158°F
      • Enclosure Rating: IP65
    • POWER SUPPLY REQUIREMENTS 
      • 20-28V AC/DC, 50/60 Hz, 5 VA maximum
    • ISOLATED ANALOG OUTPUT 
      • Maybe programmable for energy rate, flow rate, supply temperature, return temperature or Δt
      • Configurable as: 4-20mA, 0-5 V or 0-10 V output
    • ISOLATED TOTALIZING SOLID STATE CONTACT CLOSURE PULSE OUTPUTS
      • Maybe programmed for energy, volume, alarm indication, mode indication or MODBUS coil indication
      • Contact ratings: 50 mA, 30 V
      • Contact pulse duration: 50, 100, 500 or 1000 ms
    • ISOLATED TOTALIZING PULSE INPUTS 
      • For use with sinking open collector or dry contact outputs
      • Input rating: 30 VDC, 10 mA maximum
      • Pulse duration: 50 ms minimum
    • NETWORK CONNECTIONS
      • Isolated RS485 serial interface
    • COMMUNICATION PROTOCOLS 
      • BACnet® MS/TP per ASHRAE Standard 135.1: 2009
      • MODBUS® RTU
    • NETWORK CONFIGURATION & ADDRESSING
      • Baud Rates: 4800, 9600, 19200, 38400, 76800, or 115200
      • Device Address Range: 1 – 255 (1 – 247 MODBUS® RTU)
      • Device Instance Range: 1 – 4,194,303 (BACnet® only)
      • Parity: None, Even, Odd (MODBUS® RTU only)
    For further information please contact : marketing@wmablog.com