Cari

  • ONICON F-5500 Series Thermal Mass Flow Meters

    DESCRIPTION

    ONICON’s F-5500 Series Thermal Mass Flow Meters mampu memberikan pengukuran flow yang akurat untuk material natural gas, udara bertekanan tinggi, dan industrial gas lainnya. Desain perangkat sensor mengukur mass flow secara langsung dan tidak membutuhkan tambahan tekanan atau kompensasi suhu dalam penggunaannya.
    F-5500 tersedia dalam tipe inline maupun instertion dan dilengkkapi dengan interface yang mudah digunakan. Versi standar flow meter ini menggunakan 4-20 mA analog output dan interface RS485 yang kompatibel dengan BACnet® MS/TP or Modbus® RTU.  Konfigurasi signal output yang tersedia menggunakan 4-20 mA analog output dan sebuah programmable pulse output. Model pulse output nya juga tersedia dengan HART.

    APPLICATIONS

    Accurate sub-metering of natural gas & propane for:
    • Tenant space usage
    • Boiler efficiency
    • Campus monitoring
    Also ideal for monitoring:
    • Compressed Air
    • Medical gases
    • Other industrial gases

    GENERAL SPECIFICATIONS

    FLOW ACCURACY
    Natural Gas / Propane Gas
    ± 1.0% of reading from 500 – 7000 SFPM
    ± 2.0% of reading from 100 – 500 SFPM
    Compressed Air & other high-velocity calibrations
    ± 1.0% of reading + 0.5% of scale over a 100:1
    turndown
    TEMPERATURE ACCURACY
    ± 1.0°F over the range of -40 to 250° F
    OVERALL FLOW RANGE
    15 to 35,000 SFPM
    OPERATING RANGE FOR COMMON PIPE SIZES15 to 7000 SFPM in schedule 40 pipe
    Pipe Size (Inches)Flow Rate (SCFH)
    MinMax
    ¾3.31,560
    15.42,521
    9.34,362
    135,938
    2219,740
    3013,964
    34621,562
    48037,130
    512558,350
    618184,263
    8313145,912

    FEATURES

    BACnet MS/TP or MODBUS RTU –
    The standard F-5500 includes an RS485 output that provides BACnet MS/TP or Modbus RTU. Data reported to the network includes flow rate and total, temperature
    and elapsed time since reset.
    User-Friendly Interface / Display – 
    The bright, easy-to-read, backlit display and intuitive menu structure simplify page navigation and allow for field programming. Free utility software is also available for programming
    and data logging.
    Provides for Field Validation of Calibration –
    F-5500 internal diagnostic functions include a zero flow calibration check. This fast, easy to perform, the test allows for field validation of the factory zero flow calibration. The utility software provided with the meter allows you to print a certificate validating the test results. Insertion Meters Can Be Installed Without Interrupting
    Gas Service* –
    ONICON’s hot tap design allows for installation without interruption to the gas service. The meter can also be removed for service without disrupting the flow.
    Highly Accurate Over a Wide Operating Range –
    Our proprietary direct digital control sensing circuitry is very stable yet highly responsive to changes inflow. This design allows for accurate flow measurement over a very wide operating range (over 1000:1 for the inline version). It also makes the meter ideal for measuring low flow rates.
    Excellent Value –
    ONICON insertion style meters are accurate, easy-to-use and reliable. They are also priced independently of pipe size. This makes them an excellent value, particularly in larger diameter pipes.
    CALIBRATION
    Every ONICON flow meter is wet calibrated in a flow laboratory against standards that are directly traceable to NIST. A certificate of calibration accompanies every meter.
    * Installations must comply with federal, state and municipal building codes. Review all proposed combustible gas installations with your local code enforcement officials before attempting any installation.
    METHOD
    Thermal mass flow utilizing direct digital control sensing circuitry
    PIPE SIZE RANGE
    Insertion style – 1½” through 24” nominal diameter
    Inline style – ¾” through 6” nominal diameter
    INPUT POWER
    12 – 28 VDC, 6W minimum power
    FLUID TEMPERATURE RANGE
    -40° F to 250° F
    AMBIENT TEMPERATURE RANGE
    -40° F to 158° F
    MAXIMUM OPERATING PRESSURE
    Insertion flow meter:
    Standard process adapter fitting – 60 PSIG (4.1 barg) max
    High-pressure adapter fitting – 150 PSIG (10.3 barg) max
    Inline flow meter:
    Flanged-ANSI 150 (230 PSIG at 100˚ F (16 barg))
    NPT 300 PSIG (20.7 barg)
    All stainless steel ferrules
    PRESSURE DROP (@ 2500 SFPM, 70° F, and 2 PSIG)
    Insertion meter – Less than 0.5” W.C. (H20) in 1½” diameter
    pipes, decreasing in larger pipes
    Inline meter – (with built-in flow conditioner)
    Less than 0.5” W.C (H20) in 2” and larger diameter meters
    Less than 0.9” W.C (H20) in 1” and 1½” diameter meters
    PROGRAMMING / MEMORY
    Factory programmed for specific applications. Field programming available through the user interface or mini-USB interface and utility program. Non-volatile memory retains all program parameters and totalized values in the event of power loss.
                                                   other articles:

    OUTPUT SIGNALS PROVIDED
    Analog outputs: 4-20 mA (standard on all models) Select from one of the following options as the second
    output:
    • RS485 interface: BACnet MS/TP or Modbus RTU
    (field selectable)
    • Programmable pulse output: Field selectable as scaled
    pulse or alarm (Isolated open collector output)
    • 4-20 mA with HART FSK (Only available with
    programmable pulse output)
    MATERIAL
    Wetted metal components: 316 stainless steel
    ELECTRICAL CONNECTIONS
    Enclosed terminal blocks, cable access through two ¾” NPT
    conduit fittings
    APPROVALS
    FM (USA) FMc (CAN): Approved
    Class 1, Div 1, Groups B, C, D;
    Class 2, Div 2, Groups E, F, G;
    Class 3, Div 1; T4, Ta = -40˚ C to 70˚ C;
    Class 1, Zone 1, AEx/Ex db IIB + H2 T4;
    Gb Ta = -40˚ C to 70˚ C;
    Type 4X, IP66/67
    CE Mark
    EMC Directive; 2014/30/EU
    Emissions and Immunity Testing:
    EN61326-1:2013
    Massachusetts Board of State Examiners of Plumbers and Gasfitters