Cari

  • Brainchild BTC-401/402 Analog Controller

    This analog controller is used for simple applications with on/off or P control, with deviation indication.

    Feature

    • Build-in Laser Trim ASIC
    • Easy to change the range
    • ON-OFFor time proportional selectable
    • Compact, only 53mm in depth
    • A wide selection of control output option
    • A wide selection of ranges
    • Safety: UL, CSA
    • EMC, LVD: CE
      Another Article:

    Specification

    Input

    Thermocouple (T/C)Type J, K
    RTD3-wires PT 100 ohms, DIN or JIS
    RangeSee ordering information
    Accuracy±2% of span (BTC-402, BTC-401),
    ±1% of span (BTC-404)
    Cold Junction Compensation±0.1°C / 1°C
    Rejection of RTD Lead Resistance( 0.1°C – 0.025% of PV reading) / ohm
    Sensor Break ProtectionUpscale
    External Resistance100 ohms max.
    Normal Mode Rejection60 dB
    Common Mode Rejection120 dB
    Sample Rate3 times / second

    Control

    Proportion Band2.2% of span
    ON-OFF Hysteresis1 % of span
    Cycle Time20 seconds for relay output, 1 second for pulsed voltage output, 0.02 second for linear current or voltage output.
    Control ActionReverse action

    Output

    ControlRelay 5A / 240V max. resistive load
    Pulsed Voltage20mA / 32VDC max.
    Current4-20mA, 0-20mA, max. load 500 ohms
    Voltage0- 10V, min. load 500k ohms
    AlarmRelay output, 2A / 240VAC max. resistive load

    Adjustment

    SetpointSingle turn wire-wound potentiometer
    AlarmDeviation alarm, adjustable ±10% of span
    Manual ResetAdjustable 2.6% of span (BTC-404, 402 only)
    Resolution of set point0.2% of span
    Accuracy of set point±2% of span
    Repeatability of set point±0.1 % of span

    Indication

    Process IndicatorBTC-402: Deviation meter
    BTC-404: 0.5” red 3-1/2 dight LED display
    Status IndicatorON red LED Lamp
    Alarm IndicatorON red LED Lamp

    Power

    RatingBTC-402,
    BTC-401: 100-130VAC or 200-240VAC,50 / 60Hz
    ConsumptionLess than 5VA
    ENVIRONMENTAL & PHYSICAL
    Operating Temperature0-50°C
    Humidity0 to 90% RH (non-condensing)
    Insulation20M ohms min. (500VDC)
    BreakdownAC2000V,50/60Hz,1 minute
    Vibration10-55Hz,amplitude 1mm
    Shock200 m/s² (20g)
    WeightBTC-404: 280 grams,
    BTC-402: 360 grams,
    BTC-401: 330 grams
    Dimension96(W)X96(H)X53mm (depth behind the panel)
    Panel cutout92 X 92mm
  • Entri Populer

    Entri yang Diunggulkan

    JASON INDUSTRIAL

    Founded in 1958 in Fairfield, NJ, Jason Industrial quickly gained a solid reputation as a go to source for both industrial hose and power tr...